Transfer switch or interlock: troubleshooting and fixes

Find what it is doing, start at step 1 under it, and follow the steps. The app asks the same steps one question at a time.

Checked against official sources. Not yet reviewed by a licensed professional or tested by us.

Read this first

The parts

  • A: the handle, or the interlock plate on the panel
  • B: the main breaker
  • C: the generator's output breakers
  • D: the engine switch on your generator
  • E: the lights on an automatic switch
  • G: the moving parts you can see from outside
  • H: the breakers for the circuits the switch feeds

If it: The generator runs, but the house stays dead

1. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And where is the engine? Someone feels sick, dizzy or weak, or an alarm is sounding → go to 2. It's in the house, a garage, a shed or a crawlspace, or near a door, window or vent → go to 3. It's outdoors, well away from the house, and everyone feels fine → go to 4.

  • Ask everyone nearby if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Look at where the engine stands, or where you mean to start it.

2. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

3. Do this first: Don't start or run it there. If it is running, stop the engine and leave that space. Keep everyone out of that space until the air clears. When it has cooled, move it outdoors, into the open. A generator goes as far out as the entry above says. Point its exhaust away from the house. Then go to 4.

4. Is there water, smoke or sparks near it, a smell of hot insulation, or has anyone felt a shock? There's water on the floor, or it has been wet or flooded → go to 5. Smoke, sparks, a hot-insulation smell, a plate too hot to touch, or a shock → go to 6. No. It's dry, and none of that → go to 7.

  • Look at the floor where you would stand. Water that belongs there, like a sump pit, doesn't count. Water over the floor does.
  • Look and sniff around it, without touching it.
  • Ask if anyone felt a shock from it, even a mild tingle.

5. Stop. There's water on the floor, or it has been wet or flooded

6. Stop. Smoke, sparks, a hot-insulation smell, a plate too hot to touch, or a shock

7. Is the generator joined to the house wiring any way but through a transfer switch or an interlock? Yes, it's joined to the house wiring → go to 8. No. Cords run to appliances, or it's on a transfer switch → go to 9.

  • Follow each cord from the generator to its end.
  • Look for a cord into a wall outlet, a cord with a plug on both ends, or wires into the breaker panel.

8. Do this first: Set the engine switch, D, to off. Unplug that connection now. Don't connect it that way again. Then go to 9.

9. What does the switch show now? It's manual, and the handle is still on the utility or normal side → go to 10. It's automatic, and its handle or its light shows normal → go to 11. It's set to the generator, or the emergency light is on → go to 12.

  • Stay out of the enclosure. Read it from outside.
  • Look at the handle, A, or at the lights, E.
  • On most automatic switches, one light shows the normal supply and one the emergency supply.

10. Move the switch over to the generator (A). Fixed → done. Not fixed → go to 13. Can't do it → go to 13.

Careful: Live electricity.

  • Shut the generator down.
  • Set its breakers, C, to off.
  • Turn off the circuits, H, then the main, B, as the entries above say.
  • Move the handle, A, to the generator or emergency side. Don't force it.
  • It won't move? Turn the main, B, back on, then the circuits, H, and stop here.
  • Start the generator, then set its breakers, C, to on.
  • Turn on the circuits you want, H, one at a time.

11. Give the automatic switch a moment (E). Fixed → done. Not fixed → go to 14. Can't do it → go to 14.

  • Let the generator run.
  • An automatic switch waits until the generator's power has settled before it moves.
  • It waits again after the utility comes back, before it moves home.
  • Wait some minutes and watch the lights, E.

12. Does a lamp light in the generator's own outlet? No, it stays dark → go to 15. Yes, it lights, or it has no outlet of its own → go to 16.

Careful: Live output.

  • With the generator running, plug a lamp straight into its own outlet.
  • Turn the lamp on.

13. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

14. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

15. Is the generator's own output breaker on? One is off or tripped → go to 17. They're all on → go to 18.

Careful: Live output.

  • Look at the breakers on the generator's panel, C.

16. Turn that circuit's breaker on (H). Fixed → done. Not fixed → go to 19. Can't do it → go to 19.

Careful: Live electricity.

  • Stand on a dry spot, with dry hands.
  • If the handle is at off, push it to on.
  • If it sits near the middle, push it firmly to off, then to on.
  • If it trips again, leave it off and run less.

17. Turn on the generator's output breaker (C). Fixed → done. Not fixed → go to 20. Can't do it → go to 20.

Careful: Live output.

  • Set the breaker on the generator's panel, C, to on.
  • If it trips again, unplug what you can and leave it off.

18. Fix the generator first (C). Fixed → done. Not fixed → go to 21. Can't do it → go to 21.

  • Open your generator here in Fix it.
  • Pick the walk for no power coming out.
  • Come back here once a lamp lights in its own outlet.

19. What's left: The switch itself has failed.

20. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

21. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

If it: The handle or interlock won't move

1. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And where is the engine? Someone feels sick, dizzy or weak, or an alarm is sounding → go to 2. It's in the house, a garage, a shed or a crawlspace, or near a door, window or vent → go to 3. It's outdoors, well away from the house, and everyone feels fine → go to 4.

  • Ask everyone nearby if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Look at where the engine stands, or where you mean to start it.

2. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

3. Do this first: Don't start or run it there. If it is running, stop the engine and leave that space. Keep everyone out of that space until the air clears. When it has cooled, move it outdoors, into the open. A generator goes as far out as the entry above says. Point its exhaust away from the house. Then go to 4.

4. Is there water, smoke or sparks near it, a smell of hot insulation, or has anyone felt a shock? There's water on the floor, or it has been wet or flooded → go to 5. Smoke, sparks, a hot-insulation smell, a plate too hot to touch, or a shock → go to 6. No. It's dry, and none of that → go to 7.

  • Look at the floor where you would stand. Water that belongs there, like a sump pit, doesn't count. Water over the floor does.
  • Look and sniff around it, without touching it.
  • Ask if anyone felt a shock from it, even a mild tingle.

5. Stop. There's water on the floor, or it has been wet or flooded

6. Stop. Smoke, sparks, a hot-insulation smell, a plate too hot to touch, or a shock

7. Is the generator joined to the house wiring any way but through a transfer switch or an interlock? Yes, it's joined to the house wiring → go to 8. No. Cords run to appliances, or it's on a transfer switch → go to 9.

  • Follow each cord from the generator to its end.
  • Look for a cord into a wall outlet, a cord with a plug on both ends, or wires into the breaker panel.

8. Do this first: Set the engine switch, D, to off. Unplug that connection now. Don't connect it that way again. Then go to 9.

9. Turn the main off first (B). Fixed → done. Not fixed → go to 10. Can't do it → go to 10.

Careful: Live electricity.

  • Shut the generator down.
  • Set its breakers, C, to off.
  • Turn off the circuits, H, then the main, B, as the entries above say.
  • Now move the handle or slide the interlock, A. Don't force it. It holds on purpose.
  • Still won't move? Turn the main, B, back on, then the circuits, H, and stop here.
  • Start the generator, then set its breakers, C, to on.
  • Turn on the circuits you want, H, one at a time.

10. Can you see rust or dirt on the parts that move? Yes, there's rust, corrosion or dirt → go to 11. No, they look clean → go to 12.

  • Look at the handle and the moving parts you can see from outside, G.
  • Keep the enclosure shut.

11. Clean and grease the parts that move (G). Fixed → done. Not fixed → go to 13. Can't do it → go to 13.

Careful: Live electricity.

  • This is for a separate switch with its own handle. Keep grease off a panel interlock.
  • Shut the generator down, and set its breakers, C, to off.
  • Wipe the rust and dirt off the parts you can reach from outside, G.
  • Work a little electrically conductive grease into them.
  • Move the handle slowly a few times. Don't force it.
  • Now move it to the generator side.
  • Start the generator, then set its breakers, C, to on.
  • Turn on the circuits you want, H, one at a time.

No spare? It still won't move? Leave it, and run appliances from the generator by outdoor-rated cord.

12. What's left: The switch itself has failed.

13. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

If it: The power is back, but it's still on the generator

1. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And where is the engine? Someone feels sick, dizzy or weak, or an alarm is sounding → go to 2. It's in the house, a garage, a shed or a crawlspace, or near a door, window or vent → go to 3. It's outdoors, well away from the house, and everyone feels fine → go to 4.

  • Ask everyone nearby if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Look at where the engine stands, or where you mean to start it.

2. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

3. Do this first: Don't start or run it there. If it is running, stop the engine and leave that space. Keep everyone out of that space until the air clears. When it has cooled, move it outdoors, into the open. A generator goes as far out as the entry above says. Point its exhaust away from the house. Then go to 4.

4. Is there water, smoke or sparks near it, a smell of hot insulation, or has anyone felt a shock? There's water on the floor, or it has been wet or flooded → go to 5. Smoke, sparks, a hot-insulation smell, a plate too hot to touch, or a shock → go to 6. No. It's dry, and none of that → go to 7.

  • Look at the floor where you would stand. Water that belongs there, like a sump pit, doesn't count. Water over the floor does.
  • Look and sniff around it, without touching it.
  • Ask if anyone felt a shock from it, even a mild tingle.

5. Stop. There's water on the floor, or it has been wet or flooded

6. Stop. Smoke, sparks, a hot-insulation smell, a plate too hot to touch, or a shock

7. Is the generator joined to the house wiring any way but through a transfer switch or an interlock? Yes, it's joined to the house wiring → go to 8. No. Cords run to appliances, or it's on a transfer switch → go to 9.

  • Follow each cord from the generator to its end.
  • Look for a cord into a wall outlet, a cord with a plug on both ends, or wires into the breaker panel.

8. Do this first: Set the engine switch, D, to off. Unplug that connection now. Don't connect it that way again. Then go to 9.

9. Is it a manual switch or an automatic one? Manual, with a handle or an interlock → go to 10. Automatic → go to 11.

  • Look for a handle you throw by hand, A.

10. Put the switch back by hand (A). Fixed → done. Not fixed → go to 12. Can't do it → go to 12.

Careful: Live electricity.

  • Set the generator's breakers, C, to off.
  • Turn off the circuits, H.
  • On an interlock, turn the generator's breaker in the panel off first.
  • Move the handle, A, or slide the interlock, back to the normal side. Don't force it.
  • Turn the main, B, on as the entry above says.
  • Turn the circuits, H, back on one at a time.
  • Shut the generator down.

11. Give the automatic switch a moment (E). Fixed → done. Not fixed → go to 13. Can't do it → go to 13.

  • Let the generator run.
  • An automatic switch waits until the generator's power has settled before it moves.
  • It waits again after the utility comes back, before it moves home.
  • Wait some minutes and watch the lights, E.

12. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

13. What's left: The switch itself has failed.

How to get by

Sources

  • TM 5-685 / NAVFAC MO-912, Operation, Maintenance and Repair of Auxiliary Generators, para 5-5, pp. 5-13 to 5-15
  • UFC 3-540-07, Unified Facilities Criteria: Operation and Maintenance (O&M): Generators, paras 2-10, 2-11 and 5-2.11.4
  • FEMA P-1019, Emergency Power Systems for Critical Facilities: A Best Practices Approach to Improving Reliability, Section 5.2; Chapter 7; Appendix D
  • Stationary Generators: The Carbon Monoxide Poisoning Hazard and Recommendations for Mitigation (CPSC staff report), Introduction
  • Working Safely with Electricity (OSHA FactSheet, DOC FS-3942 02/2018), Generators