Minuteman

Fix it

Standby generator: troubleshooting and fixes

Find what it is doing, start at step 1 under it, and follow the steps. The app asks the same steps one question at a time.

Checked against official sources. Not yet reviewed by a licensed professional or tested by us.

Read this first

The parts

  • A: the lid of the case
  • B: the air openings in the case
  • C: the exhaust outlet
  • D: the Off and Auto switch, under the lid
  • E: the control panel
  • F: the output breaker
  • G: the oil dipstick and filler
  • H: the breaker that feeds the battery charger
  • J: the gas line, and the tank if it runs on propane
  • N: the starting battery and its cables
  • V: the label with the generator's watts

If it: It didn't start when the power went out

1. Is anyone feeling sick, or is a carbon monoxide alarm sounding? Someone feels sick, dizzy or weak, or an alarm is sounding → go to 2. Everyone's fine, and no alarm is sounding → go to 3.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.

2. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

3. Do you smell gas near the generator or in the house, or hear gas blowing or hissing? Yes, I smell it or hear it → go to 4. No, I don't smell or hear gas → go to 5.

  • Notice any smell of gas in the house.
  • Sniff around the generator from outside its case.
  • Listen near the gas line, J, where it comes to the generator.

4. Stop. Yes, I smell it or hear it

5. Has the engine run in the last little while? Yes, or I can feel heat → go to 6. No, it's cool → go to 7.

  • Hold your hand near the exhaust outlet and the case, without touching them.
  • Feel for heat.

6. Do this first: Set the switch, D, to off. Let it cool before you work on it. Set the switch back to Auto when you finish, whatever you find. Then go to 7.

7. Set the switch to Auto (D). Fixed → done. Not fixed → go to 8. Can't do it → go to 8.

  • Open the lid, A, and find the switch, D.
  • If it's on off, set it to Auto.
  • Close the lid.
  • If the power is out, it should start by itself after a moment.

8. Is its gas getting to it? The propane tank is low, or its valve is shut → go to 9. A burner in the house won't light either → go to 10. There's gas → go to 11.

  • Propane? Read the tank's gauge, and see if the tank's valve is open.
  • Natural gas and you smell gas in the house? Strike nothing. Go back and answer the gas question.
  • Natural gas and no smell? See if a gas burner in the house lights with a match. If it doesn't light at once, turn the burner off.

9. What's left: The propane tank is empty, or its valve is shut.

10. What's left: The natural gas isn't reaching the house.

11. Are the battery terminals clean and tight? There's crust, or a cable moves or is worn → go to 12. They're clean and tight → go to 13.

Careful: Battery acid and gas.

  • Turn off what the battery feeds, and any engine that's running. If it's on a machine that starts by itself, set its switch to off.
  • Look at both battery terminals, N, for white or green crust.
  • Move each cable gently at the battery. A cable that moves is loose.
  • Look along each cable for worn covering and breaks.
  • Set any switch you turned off back to Auto.

12. Clean and tighten the battery terminals (N). Fixed → done. Not fixed → go to 14. Can't do it → go to 14.

Careful: Battery acid and gas.

  • Turn off what the battery feeds, and any engine that's running. If it's on a machine that starts by itself, set its switch to off.
  • Wear goggles and gloves.
  • Keep flames and sparks away from the battery.
  • Stir baking soda into some water.
  • Brush it onto the crust on the terminals, N.
  • Keep the brush and the wrench from touching both battery terminals at once, or a terminal and bare metal.
  • Scrub each terminal gently with a wire brush.
  • Rinse the parts and wipe them dry.
  • Tighten each cable on its terminal.
  • Set any switch you turned off back to Auto, and try it again.

No spare? No wire brush? Scrub with a stiff brush or a rough cloth and the soda water.

13. Is the breaker for the battery charger on? It's off → go to 15. It's on → go to 16.

  • Find the breaker that feeds the battery charger, H.
  • Look at where it sits.

14. Charge the battery (N). Fixed → done. Not fixed → go to 17. Can't do it → go to 17.

Careful: Battery acid and gas.

  • Turn off what the battery feeds, and any engine that's running. If it's on a machine that starts by itself, set its switch to off.
  • Wear goggles and gloves, and keep flames and sparks away.
  • In freezing weather, take off any filler caps and look inside first.
  • Ice or frost inside means stop. Don't charge it. Choose that you can't do this one.
  • No ice? Put every cap back before you charge.
  • A sealed battery has no caps. If it sat flat in hard cold, don't charge it. Choose that you can't do this one.
  • Connect the charger to the battery, N, as the charger's manual shows.
  • Charge it until the charger shows it's full.
  • Turn the charger off and unplug it. Then unhook it.
  • Set any switch you turned off back to Auto, and try it again.

No spare? No charger, or nothing to run it from? Swap in a charged battery of the same kind and voltage.

15. Turn the charger's breaker back on (H). Fixed → done. Not fixed → go to 18. Can't do it → go to 18.

  • Set the breaker for the charger, H, to on.
  • Give the battery time to charge.
  • Check that the switch, D, is on Auto.

No spare? Charge the battery with a separate charger if the outage is on now.

16. Does the control panel show a fault? Yes, it shows a fault → go to 19. No, it shows no fault → go to 20.

  • Look at the control panel, E, for a fault light or a message.

17. Swap in another battery (N). Fixed → done. Not fixed → go to 21. Can't do it → go to 21.

Careful: Battery acid and gas, Heavy.

  • Turn off what the battery feeds, and any engine that's running. If it's on a machine that starts by itself, set its switch to off.
  • Wear goggles and gloves, and keep flames and sparks away.
  • Keep the wrench from touching both battery terminals at once, or a terminal and bare metal.
  • Take the negative clamp off first, then the positive.
  • Lift the old battery out, keeping it upright.
  • Clean the clamps.
  • Set in a charged battery of the same kind and voltage.
  • Fit the positive clamp first, then the negative.
  • Tighten both.
  • Set any switch you turned off back to Auto, and try it again.

No spare? Take a charged battery of the same kind and voltage from another machine you can spare.

18. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

19. Put the cause right, then clear the fault (E). Fixed → done. Not fixed → go to 22. Can't do it → go to 22.

  • Set the switch, D, to off.
  • Read the fault on the panel, E, against your manual.
  • If it names the oil, the air, the fuel or the battery, put that right first.
  • Clear the fault the way your manual shows.
  • Set the switch back to Auto.
  • If it locks out again, leave it. Don't clear it over and over.

No spare? No manual? Check the oil, the air openings, the fuel and the battery, and put right what you find. If you find nothing, leave it locked out.

20. Charge the battery (N). Fixed → done. Not fixed → go to 23. Can't do it → go to 23.

Careful: Battery acid and gas.

How: see step 14.

21. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

22. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

23. Swap in another battery (N). Fixed → done. Not fixed → go to 24. Can't do it → go to 24.

Careful: Battery acid and gas, Heavy.

How: see step 17.

24. What's left: The control board has failed · The engine itself has failed.

If it: It starts, then stops

1. Is anyone feeling sick, or is a carbon monoxide alarm sounding? Someone feels sick, dizzy or weak, or an alarm is sounding → go to 2. Everyone's fine, and no alarm is sounding → go to 3.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.

2. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

3. Do you smell gas near the generator or in the house, or hear gas blowing or hissing? Yes, I smell it or hear it → go to 4. No, I don't smell or hear gas → go to 5.

  • Notice any smell of gas in the house.
  • Sniff around the generator from outside its case.
  • Listen near the gas line, J, where it comes to the generator.

4. Stop. Yes, I smell it or hear it

5. Has the engine run in the last little while? Yes, or I can feel heat → go to 6. No, it's cool → go to 7.

  • Hold your hand near the exhaust outlet and the case, without touching them.
  • Feel for heat.

6. Do this first: Set the switch, D, to off. Let it cool before you work on it. Set the switch back to Auto when you finish, whatever you find. Then go to 7.

7. Is its gas getting to it? The propane tank is low, or its valve is shut → go to 8. A burner in the house won't light either → go to 9. There's gas → go to 10.

  • Propane? Read the tank's gauge, and see if the tank's valve is open.
  • Natural gas and you smell gas in the house? Strike nothing. Go back and answer the gas question.
  • Natural gas and no smell? See if a gas burner in the house lights with a match. If it doesn't light at once, turn the burner off.

8. What's left: The propane tank is empty, or its valve is shut.

9. What's left: The natural gas isn't reaching the house.

10. Does the control panel show a fault? Yes, it shows a fault → go to 11. No, it shows no fault → go to 12.

  • Look at the control panel, E, for a fault light or a message.

11. Put the cause right, then clear the fault (E). Fixed → done. Not fixed → go to 13. Can't do it → go to 13.

  • Set the switch, D, to off.
  • Read the fault on the panel, E, against your manual.
  • If it names the oil, the air, the fuel or the battery, put that right first.
  • Clear the fault the way your manual shows.
  • Set the switch back to Auto.
  • If it locks out again, leave it. Don't clear it over and over.

No spare? No manual? Check the oil, the air openings, the fuel and the battery, and put right what you find. If you find nothing, leave it locked out.

12. Are its air openings and exhaust clear? Something is blocking them → go to 14. They're clear → go to 15.

  • Walk around the case.
  • Look at the air openings, B, for leaves, dirt, nests and drifted snow.
  • Look at the exhaust outlet, C, for nests or anything blocking it.

13. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

14. Clear its air openings and exhaust (B). Fixed → done. Not fixed → go to 16. Can't do it → go to 16.

  • Set the switch, D, to off.
  • Let it cool.
  • Pull leaves, nests, snow and dirt away from the openings, B, and the exhaust, C.
  • Brush off dust with a soft brush or cloth.
  • Set the switch back to Auto.

15. Is the oil up to its mark? It's low → go to 17. It's up to the mark → go to 18.

  • Set the switch, D, to off.
  • Let it cool.
  • Pull the dipstick, G, wipe it, push it in and pull it again.
  • Read the level against the marks.
  • Set the switch back to Auto.

16. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

17. Add oil (G). Fixed → done. Not fixed → go to 19. Can't do it → go to 19.

  • Set the switch, D, to off.
  • Let it cool.
  • Add the oil your manual names at the filler, G, a little at a time.
  • Check the level on the dipstick.
  • Wipe up anything spilled.
  • Set the switch back to Auto.

No spare? Short of the oil your manual names? Add what clean engine oil you have rather than run it dry.

18. Take some of the load off (V). Fixed → done. Not fixed → go to 20. Can't do it → go to 20.

  • Unplug or turn off everything on it.
  • Plug back in only what matters most.
  • Plug things in one at a time, and let each one start before the next.
  • Keep the total under the rating on the label, V.

19. What's left: That didn't fix it, and nothing else on this list fits what you found. If anything has changed, start over.

20. What's left: The engine itself has failed.

If it: It runs, but the house has no power

1. Is anyone feeling sick, or is a carbon monoxide alarm sounding? Someone feels sick, dizzy or weak, or an alarm is sounding → go to 2. Everyone's fine, and no alarm is sounding → go to 3.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.

2. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

3. Do you smell gas near the generator or in the house, or hear gas blowing or hissing? Yes, I smell it or hear it → go to 4. No, I don't smell or hear gas → go to 5.

  • Notice any smell of gas in the house.
  • Sniff around the generator from outside its case.
  • Listen near the gas line, J, where it comes to the generator.

4. Stop. Yes, I smell it or hear it

5. Has the engine run in the last little while? Yes, or I can feel heat → go to 6. No, it's cool → go to 7.

  • Hold your hand near the exhaust outlet and the case, without touching them.
  • Feel for heat.

6. Do this first: Set the switch, D, to off. Let it cool before you work on it. Set the switch back to Auto when you finish, whatever you find. Then go to 7.

7. Turn on the output breaker (F). Fixed → done. Not fixed → go to 8. Can't do it → go to 8.

  • Set the switch, D, to off, and wait for the engine to stop.
  • Open the lid, A.
  • If the output breaker, F, is off or tripped, set it to on.
  • Close the lid, A.
  • Set the switch back to Auto.
  • If it trips again, turn off some of what's on in the house.

8. Take some of the load off (V). Fixed → done. Not fixed → go to 9. Can't do it → go to 9.

  • Unplug or turn off everything on it.
  • Plug back in only what matters most.
  • Plug things in one at a time, and let each one start before the next.
  • Keep the total under the rating on the label, V.

9. What's left: The transfer switch hasn't moved.

How to get by

Sources

  • UFC 3-540-07, Unified Facilities Criteria: Operation and Maintenance (O&M): Generators, paras 2-8, 5-2.4, 5-2.10.3, 5-2.10.4
  • FEMA P-1019, Emergency Power Systems for Critical Facilities: A Best Practices Approach to Improving Reliability, Sections 5.1.2 and 5.1.2.5; Appendix D, Table D-1
  • Stationary Generators: The Carbon Monoxide Poisoning Hazard and Recommendations for Mitigation (CPSC staff report), Executive Summary; Introduction
  • TM 5-685 / NAVFAC MO-912, Operation, Maintenance and Repair of Auxiliary Generators, Chapter 2, item h; Table 3-5; Table 4-2
  • TM 9-6140-200-14, Operator's, Unit, Direct Support and General Support Maintenance Manual for Lead-Acid Storage Batteries, paras 2-5, 3-11, 3-16

Open it in Minuteman. In the app it works with no signal.