Boiler: troubleshooting and fixes

Find what it is doing, start at step 1 under it, and follow the steps. The app asks the same steps one question at a time.

Checked against official sources. Not yet reviewed by a licensed professional or tested by us.

Read this first

The parts

  • A: the thermostat on the wall
  • B: the boiler's own power switch
  • C: the gas control and its lighting label
  • D: the oil tank and its gage
  • G: the water glass on a steam boiler, with a small valve above and below it
  • H: the burner and its flame window
  • J: the gas meter and the valve beside it, outdoors
  • K: the valve on the oil line
  • L: the breaker or fuse at the panel
  • N: a radiator
  • P: the gauge for pressure and heat on a hot-water boiler
  • Q: the valve where the pipe meets a radiator
  • R: the oil burner's reset button
  • S: the air vent on a radiator, and at the ends of the steam pipes
  • T: the relief valve and its pipe
  • U: the fill valve on the cold-water pipe to the boiler
  • V: the pump on the pipe near a hot-water boiler
  • W: the drain valve at the lowest point of the boiler
  • X: the expansion tank
  • Y: the steam pipes overhead

If it: No heat at all, and it burns gas

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. Has flood water reached it, up to its burner, or reached its ducts? Yes, or I can't tell → go to 7. No. Flood water never got near it → go to 8.

  • Think back over any flood in this room since it last ran.
  • Look low on it, where the burner sits, H, for a water line, mud or silt.
  • On a furnace, look at the ducts near the floor as well.

7. What's left: Flood water reached the burner or the ducts.

8. On a steam boiler, is the water low in its glass, or out of sight? Yes, it's low, or no water shows → go to 9. No, it's at its normal line, or it has no glass → go to 10.

  • A steam boiler has a glass tube on its side, G, with water showing in it. A boiler with no glass heats water. Choose no.
  • If no water shows in the glass, or it is low, turn its power switch, B, off now, and add no water.

9. Open the glass's valves (G). Fixed → done. Not fixed → go to 11. Can't do it → go to 11.

  • Turn its power switch, B, off now, if it isn't. Add no water while it's hot.
  • Find the small valve above the glass, G, and the one below it. Don't touch the glass.
  • Both open? Choose that it didn't work.
  • Let the boiler cool.
  • Put on goggles, and stand to one side of the glass.
  • Open the shut valve slowly, the top one first.
  • Look where the water stands now.
  • At its normal line? On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off. Otherwise turn it on, and watch the glass as it heats.
  • Still low? Choose that it didn't work.
  • At its line, but still no heat once it has run a while? Choose that it didn't work.

10. Since it last worked, has anyone smelled gas, or shut off the gas at the meter, outside, or at the valve on the pipe to it? Yes, or I'm not sure → go to 12. No → go to 13.

  • Ask everyone in the house. A smell from yesterday counts.
  • Ask if anyone turned the valve at the gas meter, J, a valve outside, or the valve on the pipe to it, or if the gas company did.
  • The knob on its own gas control, C, doesn't count. Its lighting label covers that one.

11. Let it cool, then fill it slowly (U). Fixed → done. Not fixed → go to 14. Can't do it → go to 14.

  • Opened the glass's valves, and the water now stands at its normal line in the glass, G? Choose that it didn't work.
  • Turn its power switch, B, off now, if it isn't.
  • Don't add any water while the boiler is hot. Cold water in a hot boiler can crack it.
  • Let it cool, however long that takes.
  • Find its normal water line, marked on the boiler or its label. No mark to go by? Choose that you can't do this one. Too much water is a danger too.
  • Open the fill valve on the cold-water pipe to the boiler, U, slowly.
  • Watch the glass, G. Close the valve when the water reaches that line.
  • On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off.
  • Otherwise turn the switch on, and watch the glass as it heats.
  • If the level falls again, turn the switch off and choose that it didn't work. Water is leaving somewhere.
  • The water holds at its line, but still no heat once it has run a while? Choose that it didn't work.

12. What's left: The gas was shut off, or someone smelled it.

13. Is the pilot flame burning? The pilot is out → go to 15. It's burning, it lights itself, or it has no pilot → go to 16. Can't check? → go to 17.

  • Smell for gas first. At any smell, stop here, leave the house, and go back to the first question.
  • Find the lighting label on the gas control, C, and the window by the burner, H.
  • Look for the small flame the label shows. A burner with no pilot has none to see.
  • If the label says the pilot or burner lights itself, or not to light it by hand, there is no pilot for you to light. Choose that.

14. What's left: Water is leaving the boiler or its pipes · The automatic water feeder isn't feeding · The water is right now, and it still won't heat.

15. Light the pilot by the label (C). Fixed → done. Not fixed → go to 18. Can't do it → go to 18.

  • Smell for gas first. At any smell, stop, do what the entry above says, and leave this burner alone.
  • Find the lighting label on the gas control, C. Read all of it first.
  • Follow only the steps on the label to light the pilot.
  • Look at the flame. It must wrap the tip of the thin metal rod beside it, the thermocouple.
  • If it won't light, or goes out again, choose that you can't do this one.

16. Do the lights work in the rest of the house? No, the power is out → go to 19. Yes, the lights work → go to 20.

  • Try a light in another room.
  • Try the light nearest it, if there is one.

17. Do the lights work in the rest of the house? No, the power is out → go to 21. Yes, the lights work → go to 22.

How: see step 16.

18. What's left: The pilot won't stay lit.

19. What's left: The house has no power.

20. Is its breaker on, and its fuse good? It's off, in the middle, or the fuse is blown → go to 23. It's on, and the fuse is good → go to 24. Can't check? → go to 25.

Careful: Live electricity.

  • If the floor by the panel is wet, don't go to it. Choose that you can't check this.
  • Stand on a dry spot, with dry hands.
  • Open the panel door, L. Leave the cover behind it on.
  • Find the handle or fuse for this machine, if it's labeled.
  • Look for a handle at off, or just short of on, or a blown fuse.

21. What's left: The house has no power.

22. Is its breaker on, and its fuse good? It's off, in the middle, or the fuse is blown → go to 26. It's on, and the fuse is good → go to 27. Can't check? → go to 28.

Careful: Live electricity.

How: see step 20.

23. Reset the breaker (L). Fixed → done. Not fixed → go to 29. Can't do it → go to 29.

Careful: Live electricity.

  • If the floor by the panel is wet, don't go to it. Say you can't.
  • Stand on a dry spot, with dry hands.
  • If the handle is at off, push it to on.
  • If it sits near the middle, push it firmly to off, then to on.
  • For a blown fuse, turn off what's on that circuit and screw in a new fuse of the same size. Put nothing else in the holder.
  • If it trips again, stand clear and leave it off.

24. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 30. Can't do it → go to 30.

  • Look at the thermostat, A. Already set to heat, and warmer than the room? Choose that it didn't work.
  • Set it to heat, the way its own instructions show.
  • Set it a few degrees warmer than the room.
  • Give it a few minutes. Listen for the burner to start.
  • Doesn't start? Choose that it didn't work.

25. With the thermostat set warmer, does the burner light? The burner doesn't light → go to 31. It lights → go to 32. Can't check? → go to 33.

  • Smell for gas first. At any smell, stop, leave the house, and go back to the first question.
  • Set the thermostat, A, a few degrees warmer than the room.
  • Watch the burner's window, H, or listen for it to light.

26. Reset the breaker (L). Fixed → done. Not fixed → go to 34. Can't do it → go to 34.

Careful: Live electricity.

How: see step 23.

27. With the thermostat set warmer, does the burner light? The burner doesn't light → go to 35. It lights → go to 36. Can't check? → go to 37.

How: see step 25.

28. With the thermostat set warmer, does the burner light? The burner doesn't light → go to 38. It lights → go to 39. Can't check? → go to 40.

How: see step 25.

29. What's left: Something on this circuit keeps tripping it.

30. With the thermostat set warmer, does the burner light? The burner doesn't light → go to 41. It lights → go to 42. Can't check? → go to 43.

How: see step 25.

31. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 44. Can't do it → go to 44.

How: see step 24.

32. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water.

33. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 45. Can't do it → go to 45.

How: see step 24.

34. What's left: Something on this circuit keeps tripping it.

35. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 46. Can't do it → go to 46.

How: see step 24.

36. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water.

37. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 47. Can't do it → go to 47.

How: see step 24.

38. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 48. Can't do it → go to 48.

How: see step 24.

39. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water.

40. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 49. Can't do it → go to 49.

How: see step 24.

41. Turn its power switch on (B). Fixed → done. Not fixed → go to 50. Can't do it → go to 50.

  • Find its own switch, B. It often looks like a light switch, on it, on the wall beside it, or at the top of the stairs.
  • Already on, or no switch to find? Choose that it didn't work.
  • Ask who turned it off, and why. If it was for a gas smell, smoke, water or a fault, leave it off and choose that you can't do this one.
  • Turn the switch on.
  • Give it a few minutes. Listen for the burner to start.
  • Doesn't start? Choose that it didn't work.

42. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water.

43. Turn its power switch on (B). Fixed → done. Not fixed → go to 51. Can't do it → go to 51.

How: see step 41.

44. Turn its power switch on (B). Fixed → done. Not fixed → go to 52. Can't do it → go to 52.

How: see step 41.

45. Turn its power switch on (B). Fixed → done. Not fixed → go to 53. Can't do it → go to 53.

How: see step 41.

46. Turn its power switch on (B). Fixed → done. Not fixed → go to 54. Can't do it → go to 54.

How: see step 41.

47. Turn its power switch on (B). Fixed → done. Not fixed → go to 55. Can't do it → go to 55.

How: see step 41.

48. Turn its power switch on (B). Fixed → done. Not fixed → go to 56. Can't do it → go to 56.

How: see step 41.

49. Turn its power switch on (B). Fixed → done. Not fixed → go to 57. Can't do it → go to 57.

How: see step 41.

50. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 58. Can't do it → go to 58.

  • Smell for gas first. At any smell, stop, and leave it alone.
  • Turn the thermostat, A, off, or all the way down.
  • Wait a few minutes.
  • Set it back to heat, a few degrees warmer than the room.
  • Listen for the burner to try. Do this once.
  • If it doesn't light, leave it, and choose that it didn't work.

51. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 59. Can't do it → go to 59.

How: see step 50.

52. Reset the breaker (L). Fixed → done. Not fixed → go to 60. Can't do it → go to 60.

Careful: Live electricity.

How: see step 23.

53. Reset the breaker (L). Fixed → done. Not fixed → go to 61. Can't do it → go to 61.

Careful: Live electricity.

How: see step 23.

54. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 62. Can't do it → go to 62.

How: see step 50.

55. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 63. Can't do it → go to 63.

How: see step 50.

56. Reset the breaker (L). Fixed → done. Not fixed → go to 64. Can't do it → go to 64.

Careful: Live electricity.

How: see step 23.

57. Reset the breaker (L). Fixed → done. Not fixed → go to 65. Can't do it → go to 65.

Careful: Live electricity.

How: see step 23.

58. What's left: Its ignition, or the control that watches its flame, has failed.

59. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · Its ignition, or the control that watches its flame, has failed · The hot-water system is short of water.

60. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 66. Can't do it → go to 66.

How: see step 50.

61. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 67. Can't do it → go to 67.

How: see step 50.

62. Light the pilot by the label (C). Fixed → done. Not fixed → go to 68. Can't do it → go to 68.

How: see step 15.

63. Light the pilot by the label (C). Fixed → done. Not fixed → go to 69. Can't do it → go to 69.

How: see step 15.

64. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 70. Can't do it → go to 70.

How: see step 50.

65. Turn the thermostat off, then on again (A). Fixed → done. Not fixed → go to 71. Can't do it → go to 71.

How: see step 50.

66. What's left: Something on this circuit keeps tripping it · Its ignition, or the control that watches its flame, has failed.

67. What's left: Something on this circuit keeps tripping it · The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · Its ignition, or the control that watches its flame, has failed · The hot-water system is short of water.

68. What's left: Its ignition, or the control that watches its flame, has failed · The pilot won't stay lit.

69. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · Its ignition, or the control that watches its flame, has failed · The hot-water system is short of water · The pilot won't stay lit.

70. Light the pilot by the label (C). Fixed → done. Not fixed → go to 72. Can't do it → go to 72.

How: see step 15.

71. Light the pilot by the label (C). Fixed → done. Not fixed → go to 73. Can't do it → go to 73.

How: see step 15.

72. What's left: Something on this circuit keeps tripping it · Its ignition, or the control that watches its flame, has failed · The pilot won't stay lit.

73. What's left: Something on this circuit keeps tripping it · The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · Its ignition, or the control that watches its flame, has failed · The hot-water system is short of water · The pilot won't stay lit.

If it: No heat at all, and it burns oil

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. Has flood water reached it, up to its burner, or reached its ducts? Yes, or I can't tell → go to 7. No. Flood water never got near it → go to 8.

  • Think back over any flood in this room since it last ran.
  • Look low on it, where the burner sits, H, for a water line, mud or silt.
  • On a furnace, look at the ducts near the floor as well.

7. What's left: Flood water reached the burner or the ducts.

8. On a steam boiler, is the water low in its glass, or out of sight? Yes, it's low, or no water shows → go to 9. No, it's at its normal line, or it has no glass → go to 10.

  • A steam boiler has a glass tube on its side, G, with water showing in it. A boiler with no glass heats water. Choose no.
  • If no water shows in the glass, or it is low, turn its power switch, B, off now, and add no water.

9. Open the glass's valves (G). Fixed → done. Not fixed → go to 11. Can't do it → go to 11.

  • Turn its power switch, B, off now, if it isn't. Add no water while it's hot.
  • Find the small valve above the glass, G, and the one below it. Don't touch the glass.
  • Both open? Choose that it didn't work.
  • Let the boiler cool.
  • Put on goggles, and stand to one side of the glass.
  • Open the shut valve slowly, the top one first.
  • Look where the water stands now.
  • At its normal line? On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off. Otherwise turn it on, and watch the glass as it heats.
  • Still low? Choose that it didn't work.
  • At its line, but still no heat once it has run a while? Choose that it didn't work.

10. Does the gage on the oil tank show oil? It reads empty or nearly, or I can't read it → go to 12. It shows oil → go to 13.

  • Find the oil tank, D, and the gage on top of it.
  • Some gages read only roughly. Near empty counts as empty.

11. Let it cool, then fill it slowly (U). Fixed → done. Not fixed → go to 14. Can't do it → go to 14.

  • Opened the glass's valves, and the water now stands at its normal line in the glass, G? Choose that it didn't work.
  • Turn its power switch, B, off now, if it isn't.
  • Don't add any water while the boiler is hot. Cold water in a hot boiler can crack it.
  • Let it cool, however long that takes.
  • Find its normal water line, marked on the boiler or its label. No mark to go by? Choose that you can't do this one. Too much water is a danger too.
  • Open the fill valve on the cold-water pipe to the boiler, U, slowly.
  • Watch the glass, G. Close the valve when the water reaches that line.
  • On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off.
  • Otherwise turn the switch on, and watch the glass as it heats.
  • If the level falls again, turn the switch off and choose that it didn't work. Water is leaving somewhere.
  • The water holds at its line, but still no heat once it has run a while? Choose that it didn't work.

12. Fill the oil tank (D). Fixed → done. Not fixed → go to 15. Can't do it → go to 15.

  • Turn its power switch, B, off.
  • Fill the tank, D, with the heating oil it takes, the kind named on the tank or the burner.
  • Look at the gage. It should show oil now.
  • Look along the line and at the tank for any drip. At a drip, leave the switch off and choose that you can't do this one.
  • Turn the switch on. Give it a few minutes.
  • A burner that ran dry stops itself, and needs its reset, R, pressed. If anyone has pressed it since it stopped, don't. Choose that it didn't work.
  • Otherwise, let it sit a few minutes, so the control cools. Stand to one side of the burner, not in front of any door on it.
  • Press the reset once, and let go. Never hold it in.
  • If it doesn't light, or rumbles, puffs or smokes, turn the switch off. Don't press it again. Choose that it didn't work.

No spare? No oil to put in? Leave the switch off, so it doesn't run the pump dry.

13. Is the valve on the oil line open? A valve has been shut by hand → go to 16. A weight or lever has dropped, or a link has parted → go to 17. They're open, or I can't find a valve → go to 18.

  • Follow the oil line from the tank to the burner. Look for a valve at each end, K.
  • Look at whether each handle is open or shut.
  • Look for a weight or lever that has dropped, or a wire link that has parted, on a valve near the burner.

14. What's left: Water is leaving the boiler or its pipes · The automatic water feeder isn't feeding · The water is right now, and it still won't heat.

15. What's left: It ran dry, and the line has air in it, or the burner is soaked.

16. Open the valve on the oil line (K). Fixed → done. Not fixed → go to 19. Can't do it → go to 19.

  • If a weight or lever has dropped, or a link has parted, leave that valve shut, and choose that you can't do this one.
  • Ask who shut the valve, and why. If it was for a leak, a flood or a fire, leave it shut, and choose that you can't do this one.
  • Open the valve, K, all the way.
  • Look at the valve and along the line for oil dripping. At any drip, shut it again and choose that you can't do this one.
  • Turn its power switch, B, on. Give it a few minutes.
  • A burner that ran dry stops itself, and needs its reset, R, pressed. If anyone has pressed it since it stopped, don't. Choose that it didn't work.
  • Otherwise, let it sit a few minutes, so the control cools. Stand to one side of the burner, not in front of any door on it.
  • Press the reset once, and let go. Never hold it in.
  • If it doesn't light, or rumbles, puffs or smokes, turn the switch off. Don't press it again. Choose that it didn't work.

17. What's left: The fire valve on the oil line has closed.

18. Do the lights work in the rest of the house? No, the power is out → go to 20. Yes, the lights work → go to 21.

  • Try a light in another room.
  • Try the light nearest it, if there is one.

19. What's left: It ran dry, and the line has air in it, or the burner is soaked.

20. What's left: The house has no power.

21. Is its breaker on, and its fuse good? It's off, in the middle, or the fuse is blown → go to 22. It's on, and the fuse is good → go to 23. Can't check? → go to 24.

Careful: Live electricity.

  • If the floor by the panel is wet, don't go to it. Choose that you can't check this.
  • Stand on a dry spot, with dry hands.
  • Open the panel door, L. Leave the cover behind it on.
  • Find the handle or fuse for this machine, if it's labeled.
  • Look for a handle at off, or just short of on, or a blown fuse.

22. Reset the breaker (L). Fixed → done. Not fixed → go to 25. Can't do it → go to 25.

Careful: Live electricity.

  • If the floor by the panel is wet, don't go to it. Say you can't.
  • Stand on a dry spot, with dry hands.
  • If the handle is at off, push it to on.
  • If it sits near the middle, push it firmly to off, then to on.
  • For a blown fuse, turn off what's on that circuit and screw in a new fuse of the same size. Put nothing else in the holder.
  • If it trips again, stand clear and leave it off.

23. With the thermostat set warmer, does the burner light? The burner doesn't light → go to 26. It lights → go to 27. Can't check? → go to 28.

  • Smell for gas first. At any smell, stop, leave the house, and go back to the first question.
  • Set the thermostat, A, a few degrees warmer than the room.
  • Watch the burner's window, H, or listen for it to light.

24. With the thermostat set warmer, does the burner light? The burner doesn't light → go to 29. It lights → go to 30. Can't check? → go to 31.

How: see step 23.

25. What's left: Something on this circuit keeps tripping it.

26. Since the burner stopped, has anyone pressed its reset button? Yes, or I'm not sure → go to 32. No → go to 33.

  • Find the reset button on the burner, R. It's on the box of controls on the burner, often red.
  • Ask everyone in the house. Once counts.

27. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water.

28. Since the burner stopped, has anyone pressed its reset button? Yes, or I'm not sure → go to 34. No → go to 35.

How: see step 26.

29. Since the burner stopped, has anyone pressed its reset button? Yes, or I'm not sure → go to 36. No → go to 37.

How: see step 26.

30. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water.

31. Since the burner stopped, has anyone pressed its reset button? Yes, or I'm not sure → go to 38. No → go to 39.

How: see step 26.

32. What's left: The reset has been pressed, and the burner may be soaked with oil.

33. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 40. Can't do it → go to 40.

  • Look at the thermostat, A. Already set to heat, and warmer than the room? Choose that it didn't work.
  • Set it to heat, the way its own instructions show.
  • Set it a few degrees warmer than the room.
  • Give it a few minutes. Listen for the burner to start.
  • Doesn't start? Choose that it didn't work.

34. What's left: The reset has been pressed, and the burner may be soaked with oil.

35. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 41. Can't do it → go to 41.

How: see step 33.

36. What's left: The reset has been pressed, and the burner may be soaked with oil.

37. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 42. Can't do it → go to 42.

How: see step 33.

38. What's left: The reset has been pressed, and the burner may be soaked with oil.

39. Set the thermostat warmer (A). Fixed → done. Not fixed → go to 43. Can't do it → go to 43.

How: see step 33.

40. Turn its power switch on (B). Fixed → done. Not fixed → go to 44. Can't do it → go to 44.

  • Find its own switch, B. It often looks like a light switch, on it, on the wall beside it, or at the top of the stairs.
  • Already on, or no switch to find? Choose that it didn't work.
  • Ask who turned it off, and why. If it was for a gas smell, smoke, water or a fault, leave it off and choose that you can't do this one.
  • Turn the switch on.
  • Give it a few minutes. Listen for the burner to start.
  • Doesn't start? Choose that it didn't work.

41. Turn its power switch on (B). Fixed → done. Not fixed → go to 45. Can't do it → go to 45.

How: see step 40.

42. Turn its power switch on (B). Fixed → done. Not fixed → go to 46. Can't do it → go to 46.

How: see step 40.

43. Turn its power switch on (B). Fixed → done. Not fixed → go to 47. Can't do it → go to 47.

How: see step 40.

44. Press the burner's reset button once (R). Fixed → done. Not fixed → go to 48. Can't do it → go to 48.

  • Has anyone pressed it already since the burner stopped? Then don't. Choose that you can't do this one.
  • Let it sit a few minutes after it stopped, so the control cools.
  • Stand to one side of the burner, not in front of any door on it.
  • Press the reset button, R, once, and let go. Never hold it in.
  • If it lights and runs smoothly, let it run.
  • If it rumbles, puffs or smokes, turn its switch, B, off and choose that it didn't work.
  • If it doesn't light, don't press it again. Turn the switch off and choose that it didn't work.

45. Press the burner's reset button once (R). Fixed → done. Not fixed → go to 49. Can't do it → go to 49.

How: see step 44.

46. Press the burner's reset button once (R). Fixed → done. Not fixed → go to 50. Can't do it → go to 50.

How: see step 44.

47. Press the burner's reset button once (R). Fixed → done. Not fixed → go to 51. Can't do it → go to 51.

How: see step 44.

48. What's left: The oil line or the burner itself · The burner didn't light after the reset, and may be soaked with oil.

49. What's left: The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water · The oil line or the burner itself · The burner didn't light after the reset, and may be soaked with oil.

50. Reset the breaker (L). Fixed → done. Not fixed → go to 52. Can't do it → go to 52.

Careful: Live electricity.

How: see step 22.

51. Reset the breaker (L). Fixed → done. Not fixed → go to 53. Can't do it → go to 53.

Careful: Live electricity.

How: see step 22.

52. What's left: Something on this circuit keeps tripping it · The oil line or the burner itself · The burner didn't light after the reset, and may be soaked with oil.

53. What's left: Something on this circuit keeps tripping it · The pump that moves the water has stopped · The thermostat's wiring or the burner's own controls · The hot-water system is short of water · The oil line or the burner itself · The burner didn't light after the reset, and may be soaked with oil.

If it: Some radiators stay cold

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. Has flood water reached it, up to its burner, or reached its ducts? Yes, or I can't tell → go to 7. No. Flood water never got near it → go to 8.

  • Think back over any flood in this room since it last ran.
  • Look low on it, where the burner sits, H, for a water line, mud or silt.
  • On a furnace, look at the ducts near the floor as well.

7. What's left: Flood water reached the burner or the ducts.

8. Is it a steam boiler, with a glass showing water on its side? Steam → go to 9. Hot water → go to 10.

  • A steam boiler has a glass tube on its side, G, with water in it, and its radiators have a small vent on the side.
  • A hot-water boiler has a gauge for pressure and heat, P, and a pump on its pipes.

9. When the steam comes up, does the radiator's air vent hiss, then close? It stays silent, or it spits water or steam → go to 11. It hisses, then closes → go to 12. Can't check? → go to 13.

  • Find the small air vent on the side of the radiator, S, at the end away from the pipe.
  • With the boiler making steam, stand back and listen to it. Don't touch it. It's hot.

10. Let the air out of the radiators (S). Fixed → done. Not fixed → go to 14. Can't do it → go to 14.

  • Turn the thermostat, A, down, and let the radiators cool enough to touch.
  • Start at the radiator lowest in the house.
  • Hold a small pail and a cloth under its air vent, S.
  • Open the vent a little with its key or a screwdriver. Air hisses out.
  • Close it as soon as water comes out steadily, with no air.
  • Do each radiator in turn, working up to the highest.
  • Set the thermostat back up.
  • If no water comes at the top radiators, or the gauge, P, reads lower than before, choose that it didn't work.

11. Clean the air vent (S). Fixed → done. Not fixed → go to 15. Can't do it → go to 15.

  • Turn its power switch, B, off, and let the radiators and pipes cool. A vent can spit steam and scalding water.
  • Unscrew the vent, S, by hand, or with a wrench on its base.
  • Soak it in a jar of kerosene for a day, to loosen the rust and grease.
  • Stand it upright to drain, and let it dry.
  • Put on goggles. Blow air through it with a pump or an air hose.
  • Screw it back in, upright.
  • Turn the switch on. When the steam comes up, listen for it to hiss, then close.
  • Stays silent, or spits water or steam? Choose that it didn't work.

No spare? Need heat while it soaks? Shut that radiator's valve, Q, until the vent is back in.

12. Open the radiator's valve (Q). Fixed → done. Not fixed → go to 16. Can't do it → go to 16.

  • Find the valve where the pipe meets the cold radiator, Q. No valve, or it's already open? Choose that it didn't work.
  • Turn its handle to open. On hot water it may take only a half turn.
  • On steam, open it all the way.
  • If it won't turn, don't force it. Choose that you can't do this one.
  • Give the radiator time to heat.
  • Still cold once the heat has been up a while? Choose that it didn't work.

13. Open the radiator's valve (Q). Fixed → done. Not fixed → go to 17. Can't do it → go to 17.

How: see step 12.

14. Open the radiator's valve (Q). Fixed → done. Not fixed → go to 18. Can't do it → go to 18.

How: see step 12.

15. Fit a new air vent (S). Fixed → done. Not fixed → go to 19. Can't do it → go to 19.

  • Turn its power switch, B, off, and let the radiators and pipes cool.
  • Unscrew the old vent, S.
  • Screw in a new vent of the same kind as the others on that floor, upright.
  • Turn the switch on. When the steam comes up, listen for it to hiss, then close.
  • Stays silent, or spits water or steam? Choose that it didn't work.

No spare? No new vent? Borrow the one from a radiator in a room you can close off, and shut that radiator's valve, Q.

16. What's left: The radiator slopes the wrong way · A trap, a pipe or the steam pressure.

17. Clean the air vent (S). Fixed → done. Not fixed → go to 20. Can't do it → go to 20.

How: see step 11.

18. What's left: The pump that moves the water has stopped · The hot-water system is short of water · A pipe is stopped up inside.

19. What's left: The pipe holds water at the vent.

20. Fit a new air vent (S). Fixed → done. Not fixed → go to 21. Can't do it → go to 21.

How: see step 15.

21. What's left: The radiator slopes the wrong way · A trap, a pipe or the steam pressure · The pipe holds water at the vent.

If it: Banging or hammering in the steam pipes

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. Has flood water reached it, up to its burner, or reached its ducts? Yes, or I can't tell → go to 7. No. Flood water never got near it → go to 8.

  • Think back over any flood in this room since it last ran.
  • Look low on it, where the burner sits, H, for a water line, mud or silt.
  • On a furnace, look at the ducts near the floor as well.

7. What's left: Flood water reached the burner or the ducts.

8. When the steam comes up, does the radiator's air vent hiss, then close? It stays silent, or it spits water or steam → go to 9. It hisses, then closes → go to 10. Can't check? → go to 11.

  • Find the small air vent on the side of the radiator, S, at the end away from the pipe.
  • With the boiler making steam, stand back and listen to it. Don't touch it. It's hot.

9. Clean the air vent (S). Fixed → done. Not fixed → go to 12. Can't do it → go to 12.

  • Turn its power switch, B, off, and let the radiators and pipes cool. A vent can spit steam and scalding water.
  • Unscrew the vent, S, by hand, or with a wrench on its base.
  • Soak it in a jar of kerosene for a day, to loosen the rust and grease.
  • Stand it upright to drain, and let it dry.
  • Put on goggles. Blow air through it with a pump or an air hose.
  • Screw it back in, upright.
  • Turn the switch on. When the steam comes up, listen for it to hiss, then close.
  • Stays silent, or spits water or steam? Choose that it didn't work.

No spare? Need heat while it soaks? Shut that radiator's valve, Q, until the vent is back in.

10. What's left: Water is carried up into the steam pipes · The radiator slopes the wrong way · A steam pipe sags and holds water · The pipes are only growing as they warm.

11. Is it light snapping as the pipes warm, or hard banging? Light snapping or ticking as they warm → go to 13. Hard banging or hammering → go to 14.

  • Listen as the heat comes up, from a few steps back from the pipes, Y.

12. Fit a new air vent (S). Fixed → done. Not fixed → go to 15. Can't do it → go to 15.

  • Turn its power switch, B, off, and let the radiators and pipes cool.
  • Unscrew the old vent, S.
  • Screw in a new vent of the same kind as the others on that floor, upright.
  • Turn the switch on. When the steam comes up, listen for it to hiss, then close.
  • Stays silent, or spits water or steam? Choose that it didn't work.

No spare? No new vent? Borrow the one from a radiator in a room you can close off, and shut that radiator's valve, Q.

13. What's left: The pipes are only growing as they warm.

14. Is the water high in the glass, or bouncing up and down? High, or bouncing → go to 16. Steady, at its normal line → go to 17.

  • Look at the glass tube on the side of the boiler, G, while it's making steam. Don't touch it.

15. What's left: The pipe holds water at the vent.

16. What's left: Water is carried up into the steam pipes.

17. Clean the air vent (S). Fixed → done. Not fixed → go to 18. Can't do it → go to 18.

How: see step 9.

18. Fit a new air vent (S). Fixed → done. Not fixed → go to 19. Can't do it → go to 19.

How: see step 12.

19. What's left: The radiator slopes the wrong way · A steam pipe sags and holds water · The pipe holds water at the vent.

If it: The relief valve is dripping or running

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. What's left: The relief valve is letting water or steam out · The relief valve itself · The pipe to the expansion tank is frozen or closed · The expansion tank is full of water, or short of air.

If it: Steam boiler is low in its glass, or shut off on low water

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. Open the glass's valves (G). Fixed → done. Not fixed → go to 7. Can't do it → go to 7.

  • Turn its power switch, B, off now, if it isn't. Add no water while it's hot.
  • Find the small valve above the glass, G, and the one below it. Don't touch the glass.
  • Both open? Choose that it didn't work.
  • Let the boiler cool.
  • Put on goggles, and stand to one side of the glass.
  • Open the shut valve slowly, the top one first.
  • Look where the water stands now.
  • At its normal line? On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off. Otherwise turn it on, and watch the glass as it heats.
  • Still low? Choose that it didn't work.
  • At its line, but still no heat once it has run a while? Choose that it didn't work.

7. Let it cool, then fill it slowly (U). Fixed → done. Not fixed → go to 8. Can't do it → go to 8.

  • Opened the glass's valves, and the water now stands at its normal line in the glass, G? Choose that it didn't work.
  • Turn its power switch, B, off now, if it isn't.
  • Don't add any water while the boiler is hot. Cold water in a hot boiler can crack it.
  • Let it cool, however long that takes.
  • Find its normal water line, marked on the boiler or its label. No mark to go by? Choose that you can't do this one. Too much water is a danger too.
  • Open the fill valve on the cold-water pipe to the boiler, U, slowly.
  • Watch the glass, G. Close the valve when the water reaches that line.
  • On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off.
  • Otherwise turn the switch on, and watch the glass as it heats.
  • If the level falls again, turn the switch off and choose that it didn't work. Water is leaving somewhere.
  • The water holds at its line, but still no heat once it has run a while? Choose that it didn't work.

8. What's left: Water is leaving the boiler or its pipes · The thermostat's wiring or the burner's own controls · The automatic water feeder isn't feeding · The water is right now, and it still won't heat.

If it: The power is out and the house is freezing

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. Has flood water reached it, up to its burner, or reached its ducts? Yes, or I can't tell → go to 7. No. Flood water never got near it → go to 8.

  • Think back over any flood in this room since it last ran.
  • Look low on it, where the burner sits, H, for a water line, mud or silt.
  • On a furnace, look at the ducts near the floor as well.

7. What's left: Flood water reached the burner or the ducts.

8. Drain it before it freezes (W). Fixed → done. Not fixed → go to 9. Can't do it → go to 9.

  • Turn its power switch, B, off.
  • On gas, turn its gas control, C, off the way its label shows.
  • Turn off the fill valve on the cold-water pipe to the boiler, U, so it can't fill again.
  • If it was running, let the water cool first. It can scald.
  • Run a hose from the drain valve at the lowest point of the boiler, W, to a floor drain, or outdoors and downhill.
  • Open the drain valve.
  • On hot water, open the air vents on the highest radiators, S, to let air in.
  • On steam, also open the drains at the ends of the steam pipes and on the pipes that run low along the floor.
  • Leave them open while the house is freezing.
  • When the power is back, close every drain and vent, and fill it through the fill valve. On hot water, let the air out of each radiator from the lowest up. On steam, fill to the normal water line marked on the boiler or its label, watching the glass, G.
  • On gas, if anyone has smelled gas or shut it off since it last ran, leave the switch off.
  • Otherwise, only when it's full, set a gas control, C, back on by the steps on its label, then turn its power switch, B, back on.

No spare? No hose? Catch it in buckets, and close the drain valve between them.

9. What's left: Water in the system may already have frozen.

If it: Smoke, soot or a burning or oily smell

1. Do you smell gas in the house, or hear it hissing? Yes, I smell it or hear it → go to 2. No, I don't smell or hear gas → go to 3.

  • Notice any smell of gas as you walk in.
  • If you smell it, stop there and answer yes. Don't go on to the appliance.
  • If you smell nothing, listen near the appliance, without touching anything on it.
  • If the appliance is electric, answer for the house all the same.

2. Stop. Yes, I smell it or hear it

3. Is anyone feeling sick, or is a carbon monoxide alarm sounding? And look at the pipe that carries the furnace or boiler's smoke away. Someone feels sick, dizzy or weak, or an alarm is sounding → go to 4. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room → go to 5. None of that. Everyone's fine, and the pipe is whole → go to 6.

  • Ask everyone in the house if they feel sick, dizzy or weak.
  • Listen for a carbon monoxide alarm.
  • Notice any smoke or fumes coming into the room from the furnace or boiler.
  • Follow the metal pipe from the furnace or boiler to the chimney or the wall, by eye. Don't touch it. It can be hot.
  • Look for holes, spots rusted through, joints come apart, a gap, or a stretch that runs downhill.
  • Plastic vent pipes? Follow them to where they leave the house, and look that nothing blocks their ends outside.

4. Stop. Someone feels sick, dizzy or weak, or an alarm is sounding

5. Stop. The pipe is blocked, holed, come apart or missing, or smoke is coming into the room

6. What's left: It isn't burning cleanly.

How to get by

Sources

  • TM 5-642, Operation and Maintenance: Small Heating Systems (oil and gas burners, steam and hot-water boilers, warm-air furnaces), Chapter 3, burners; chapter 4, steam boilers; chapter 5, hot-water systems
  • NAVEDTRA 10662, Utilitiesman 2 (rate training manual), chapters 9 and 10: oil-burner controls and troubleshooting, Table 9-1, hot-water relief valve, air vents, circulating pumps, troubleshooting, Chapter 9, oil-burner controls; chapter 10, hot-water heating systems
  • NAVEDTRA 12532, Utilitiesman 3 (rate training manual), chapter 9: furnace filters, furnace troubleshooting and gas burner maintenance, the pilot safety valve, Chapter 9, the pilot safety valve
  • NAVEDTRA 10662, Utilitiesman 2 (rate training manual), chapter 9: pilot light, thermocouple, relay, limit control, Chapter 9, pilot light and thermocouple
  • Oil Burners for Home Heating (Circular No. 406), Emergency or Safety Controls; Care of Burners
  • Home Heating: Systems, Fuels, Controls (Farmers' Bulletin No. 2235), Gas, pp. 20 and 21
  • Repairing Your Flooded Home (FEMA P-234 / ARC 4477): flooded ducts, the furnace blower, and flooded gas and oil appliances, Step 5
  • Power Outages and Indoor Air Quality (IAQ), Heating: Combustion Appliances

Open it in Minuteman. In the app it works with no signal.